Catalog #: AF16Z-30-22-22
Invoice Description: CTR,3P,17A,LOW48-130VAC/DC,2/2
Catalog Description: Af16z contactors are used for controlling power circuits up to 690 v AC and 220 v DC. They are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads. AF z contactors include an electronic coil interface accepting a wide control voltage uc min. UC max. only four coils cover control voltages between 24 .250 v 50/60 hz or 12 .250 v DC. AF z contactors can manage large control voltage variations. one coil can be used for different control voltages used worldwide without any coil change. AF z contactors allow direct control by plc-output 24 v DC 500 ma and obtain a reduced holding coil consumption. AF z contactors withstand short voltage dips and voltage sags (semi f47-0706 compliance) between 24 .250 v 50/60 hz AF z contactors have built-in surge protection and do not require additional surge suppressors the AF series 2-stack 3-pole contactors are of the block type design. Main poles and auxiliary contact blocks: 3 main poles with a non-removable front-mounted 2 n.o. + 2 n.c. auxiliary contact block, side-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with annex l of iec 60947-5-1 including the ""mechanically linked"" symbol on the contactor side. n.c. mirror contacts compliant with annex f of iec 60947-4-1) - control circuit: AC or DC operated - accessories: a wide range of accessories is available. note: 2-stack contactors available in some countries: please consult your abb representative.